|
Trouble
|
Cause
|
Remedial action
|
|
BURN-OUT
AI-CH0
|
The room temperature
compensation input to the temperature controller
was disconnected. The chamber has been stopped. |
The sensor is
loosely connected to the RTD terminal on the SCP-220
temperature controller board or there is an
open circuit on the SCP-220 board. |
Turn control
power OFF from the POWER
key and resume testing. If the same alarm occurs
again, call for service. |
|
BURN-OUT
AI-CH1
|
The dry-bulb
input to the temperature controller was disconnected.
The chamber has been stopped. |
The sensor is
loosely connected to the TD terminal on the SCP-220
temperature controller board or there is an
open circuit in the connected thermocouple. |
Turn control
power OFF from the POWER
key and resume testing. If the same alarm occurs
again, call for service. |
|
BURN-OUT
AI-CH2
|
The wet-bulb/humidity
input to the temperature controller was disconnected.
The chamber has been stopped. |
The sensor is
loosely connected to the TW terminal on the SCP-220
temperature controller board
or there is an open circuit in the connected thermocouple. |
Turn control
power OFF from the POWER
key and resume testing. If the same alarm occurs
again, call for service. |
BURN-OUT
AI-CH5
CH12
|
A refrigeration
circuit monitor channel (Ai5
12ch) to the temperature controller was disconnected.
The chamber has been stopped. If the backup mode
is ON and the chamber has multiple refrigerators,
only the affected refrigerator stops while all others
continue running. |
Either the sensor
is loosely connected to the Ai5
12 terminal on the SCP-220 temperature
controller board or there is an open circuit
in the connected thermocouple. |
Turn control
power OFF from the POWER
key (wait for the test end if backup mode is ON)
and resume testing. If the same alarm occurs again,
call for service. |
|
UPPER DEV.
LIMIT : TEMP.
|
The temperature
inside the chamber has risen above the upper deviation
limit. The heater has been stopped until temperature
returns within range. |
Either specimens
inside the chamber are generating heat or the upper
deviation limit is set too low. |
Remove the heat-generating
specimens and/or set the upper
deviation limit about 10°C.
When temperature returns within range, normal control
is restored automatically. The alarm can be cleared
by pressing the Buzzer
Stop key. |
|
ABS.HIGH
LIMIT : TEMP.
|
The temperature
inside the chamber has risen above the absolute
high limit. The chamber has been stopped. |
Either specimens
inside the chamber are generating heat or the absolute
high limit is set too low. |
Turn control
power OFF from the POWER
key. Then, remove the heat-generating specimens
and/or set the absolute high
limit about 15°C
higher than the target temperature. Resume testing.
If the same alarm occurs again, call for service.
|
|
|
The temperature
inside the chamber has dropped below the absolute
low limit. The chamber has been stopped. |
Possible causes include infiltrating
of outside air, excessive cooling, the effects
of cooling sources inside the chamber, and the
absolute low limit being set too high.
|
Turn control
power OFF from the
POWER
key and check the chamber door and cable ports.
If the refrigerator is on manual control, correct
the capacity setting. If cooling
sources are overcooling the chamber, reduce their
number. Also, correct the absolute low limit setting
as necessary. Then, resume testing. If the same
alarm occurs again, call for service. |
|
OVERHEATING
|
The temperature
inside the chamber has risen above the overheat
protector setting (instrumentation panel). The chamber
has been stopped. |
Either specimens
inside the chamber are generating heat or the overheat
protector is set too low. |
Turn control
power OFF from the
POWER
key. Then, remove the heat-generating specimens
and/or correct the overheat protector setting. Resume
testing. If the same alarm occurs again, it is possible
the thermal fuse has blown. Call for service. |
|
BLOWER FAILURE
|
The built-in
temperature switch of the air circulator motor (water
circuit [heat exhaust] compartment) tripped because
the motor is abnormally hot. The chamber has been
stopped. |
Overloaded air
circulator motor |
Leave the chamber
OFF until the air circulator cools down. Then, turn
control power ON from the POWER
key and resume testing. |
|
REFRIG. :
HIGH PRESSURE
FAILURE
|
The high pressure
switch tripped because refrigerator pressure was
high. The chamber has been stopped. |
The refrigerator's
operating pressure is higher than specified. |
Turn control
power OFF from the
POWER
key. With air-cooled refrigerators, check if the
condenser
filter is clogged. Correct as necessary
and resume testing. If the same alarm occurs again,
call for service. |
|
REFRIG. :
OVERCURRENT
FAILURE
|
The thermal relay
tripped because refrigerator operating current was
high. The chamber has been stopped. |
The refrigerator's
operating current is higher than specified. |
Turn control
power OFF from the
POWER
key. With air-cooled
refrigerators, check if the condenser
filter is clogged. Correct as necessary
and resume testing. If the same alarm occurs again,
call for service. |
|
REFRIG. : SURFACE
TEMP. HIGH
|
The compressor
temperature switch tripped because refrigerator
surface temperature was high. The chamber has been
stopped. |
The refrigerator's
surface temperature is higher than specified. |
Turn control
power OFF from the
POWER
key. With air-cooled refrigerators, check if
the condenser
filter is clogged. Correct as necessary
and resume testing. If the same alarm occurs again,
call for service. |
|
REFRIG. :
CONDENSER FAN
FAILURE
|
The thermal relay
of the condenser fan tripped because fan operating
current was high. The chamber has been stopped. |
The condenser
fan motor operating current is higher than specified. |
Turn control
power OFF from the
POWER
key and check if the condenser
filter is clogged. Correct as necessary
and resume testing. If the same alarm occurs again,
call for service. |
OUT-OF-RANGE
(AI-CH5
CH12)
|
A temperature
outside of the specified range was detected on one
of the temperature controller channels (Ai5
12ch) that monitor the refrigeration circuit. The
chamber has been stopped. If the chamber has more
than 1 refrigerator and the backup mode is ON, only
the affected refrigerator will shut down, while
the chamber will continue running using another
refrigerator. |
Frost buildup,
compressor trouble or a refrigerant leak are all
possible causes. |
After testing
ends, turn control power OFF and ON from the POWER
key and resume testing. If the same alarm occurs
again, call for service. |
|
HEATER FAILURE
|
The heater's
circuit protector tripped because operating current
was high. The chamber has been stopped. |
Short-circuit
or overcurrent in the heater circuit |
Set the main
power switch (leakage breaker) in the OFF position
and reset
the heater's circuit protector on the electric parts
chassis
(electric parts compartment). Then,
reactivate the system from the main power switch
followed by the POWER
key, and resume testing. If the same alarm occurs
again, call for service. |
|
|
A reverse or
open phase was detected in the 3 primary
power supply connection. The chamber has been stopped.
* A reverse or open phase can be detected
even when the POWER
key is in the OFF position. |
Primary power
supply is not correctly connected to the chamber. |
An incorrect
power supply can seriously affect chamber components.
Set the main power switch (leakage breaker)
in the OFF position, and check/correct
primary power supply phase alignment and connections.
Then, reactivate the system from the main power
switch followed by the POWER
key, and resume testing. If the same alarm occurs
again, call for service. |
|
EXT. EQUIPMENT
FAILURE
|
Trouble was detected
in an external unit. The chamber has been stopped. |
For information
on external unit troubles, see the instruction manual
that came with the external unit. |
Turn control
power OFF from the
POWER
key. Then, take the remedial action described
in the instruction manual of the external unit.
Resume testing. If the same alarm occurs again,
call for service. |
|
HUMIDIFIER
FAILURE
|
The humidifier's
circuit protector tripped because operating current
was high. The chamber has been stopped. If the backup
mode is ON, humidity tests are suspended, but temperature
tests continue. |
Short-circuit
or overcurrent in the humidifier circuit. |
Set the main
power switch (leakage breaker) in the OFF position
and reset
the humidifier's circuit protector on the electric
parts chassis (electric parts compartment).
Then, reactivate the system from the main power
switch followed by the POWER
key, and resume testing. If the same alarm occurs
again, call for service. |
|
ABS. HIGH
LIMIT : HUM.
|
The humidity
inside the chamber has risen above the absolute
high limit. The humidifier has been stopped until
humidity returns within range. |
The absolute
high limit is set too low. |
Set
the absolute high limit setting about 10%RH higher
than the humidity SV.
When humidity returns within range, normal control
is restored automatically. The alarm can be cleared
by pressing the Buzzer
Stop key. |
|
ABS. LOW
LIMIT : HUM.
|
The humidity
inside the chamber has dropped below the absolute
low limit. The heater has been stopped and refrigerator
capacity decreased to the minimum (turned OFF in
some cases) until humidity returns within range. |
The absolute
low limit is set too high. |
Set
the absolute low limit setting about 10%RH lower
than the humidity SV.
When humidity returns within range, normal control
is restored automatically. The alarm can be cleared
by pressing the Buzzer
Stop key. |
|
HUM. TRAY DRAIN
FAILURE
|
Humidifying tray
water level does not lower even though water is
being drained. The chamber has been stopped. |
Either the drainage
pump has malfunctioned or the drainage line is clogged. |
Check the water
circuit drainage pump (water circuit compartment)
is functioning correctly, and check for clogs in
the drainage line and clean as necessary. Then,
resume testing. If the same alarm occurs again,
call for service. |
|
MAIN WATER TANK
EMPTY
|
The main water
tank is empty. The humidifier has been stopped. |
The main water
tank is empty. |
Refill the auxiliary
water tank and set it on the main water tank. Then,
resume testing. After water has been sufficiently
supplied to the main water tank, the alarm can be
cleared by pressing the Buzzer
Stop key. If the same
alarm occurs again, call for service. |
|
HUMIDIFIER WATER
SUPPLY RATE1
|
The humidifying
tray did not fill within the specified amount time
at the start of humidity testing. The chamber has
been stopped. If the backup mode is ON, humidity
tests are suspended, but temperature tests continue. |
The strainer
on the humidifying water supply circuit is either
clogged or the circuit is leaking, or water supply
pressure is too low. |
Check the humidifying
water supply circuit and correct as necessary. Then,
resume testing. If the same alarm occurs again,
call for service. |
|
HUMIDIFIER WATER
SUPPLY RATE2
|
The humidifying
tray did not fill within the specified amount time
during humidity testing. The chamber has been stopped.
If the backup mode is ON, humidity tests are suspended,
but temperature tests continue. |
The strainer
on the humidifying water supply circuit is either
clogged or the circuit is leaking, or water supply
pressure is too low. |
Check the humidifying
water supply circuit and correct as necessary. Then,
resume testing. If the same alarm occurs again,
call for service. |
|
DRY WICK
|
During humidity
testing, the wet-bulb (measures relative humidity)
rose above the specified temperature. The humidifier
will continue as is, but humidity control might
destabilize and trigger a humidity alarm. |
The wet-bulb
wick (gauze) inside the chamber may be dry. |
Stop the chamber
and replace the wick. After wet-bulb temperature
returns within the specified range, the alarm can
be cleared by pressing the Buzzer
Stop key. |
|
AUX. WATER TANK
EMPTY
|
The auxiliary
water tank is empty. The humidifier will continue
on the water in the main tank, but it will eventually
stop unless water is replenished. |
The auxiliary
water tank is empty. |
Refill the auxiliary
water tank and resume testing. After water has been
sufficiently supplied to the main water tank, the
alarm can be cleared by pressing the Buzzer
Stop key. If the same
alarm occurs again, call for service. |
|
COMMUNICATION
ERROR-1-6
|
The instrumentation
detected communication trouble between the CPU board
and display board. Or the instrumentation detected
system trouble in the display board. The chamber
has been stopped. |
Communication
error between the CPU board and display board |
Reactivate the
system from the main power switch (leakage breaker)
and resume testing. If the same alarm occurs again,
call for service. |